Call Us
Call Us
08045814681
E-mail Us
Email
vikashjain@asiatic-india.com
Change Language
SP House Service Cutout

SP House Service Cutout

100-1000000 INR/Number

Product Details:

X

SP House Service Cutout Price And Quantity

  • 100-1000000 INR/Number
  • 100 Number

SP House Service Cutout Trade Information

  • 100 Number Per Month
  • 8-10 Week

Product Description

The SP House Service Cutouts are designed for 60/80/100A rating complying with BS 7657:1993 and ESI 12-10. They ensure accuracy in the various parts for interchangeability.We provide brass inserts wherever required for fixing one part to another. The Terminal Blocks are of Brass duly Tin plated, fitted with two large pinching screws per conductor. Further, these SP House Service Cutouts are designed for standard BS 88 / BS 1361 fuse links and standard copper contacts having uniform pressure to ensure effective contact with long service life.

Following dimensions are standard:
  • Upto 60/80A 22.23 mm dia.-57 mm long II a 80/100A 30.16 mm dia.-57 mm long II b Fuse Carriers.
  • Fuse link can be withdrawn from the open end of the carrier half. Carrier housing is common for both 60A & 100A fuse links. 
  • Upgrading of cutout can be done simply by replacing with larger fuse clips.

Sealing:

 

  • The fuse carrier and fuse base unit have provision for wire sealing. An additional wire sealing arrangement is provided for the neutral. 

 

Phase Protection:

 

  • A hinge type nylon shroud covers the incoming phase terminals thus reducing the possibility of accidental contact with live parts when wiring the outgoing terminal. 

 

Interlocking:

 

  • Prior to removal of any component, the fuse carrier has to be withdrawn. This enables clear access to the neutral block and/or cable trough. This is an inbuilt safety feature.

 

Terminals:
  • The design and construction of the cutouts ensures terminals to be retained without the use of any fixing screws.
  • Adequate size serrated bores and pinching screws are provided for standard Copper or Aluminum and solid conductors of upto 35 sq. mm.. The neutral/earth block of the cutout also has bores for two earth conductors and connection for a time switch wire.

Cabling:

 

  • The cable trough is designed for termination, suitable for PVC cables. In addition a small knockout is provided for an externally connected earth wire when using a PILCA cable.

 

Type Tests:
  • The cutout has been tested for the following Type Tests as per BS 7657:
  • Test for temperature rise at rated current. Mechanical endurance (including repeat of test for temperature rise at rated current).
  • Overload test (including repeat of test for temperature rise at rated current, lightning impulse withstand voltage dry tests and power frequency withstand voltage dry tests).
  • Performance under short-circuit conditions, Flammability test, Impact test, Strength of sealing lugs.
  • Degree of protection test (Ip4x) and Terminal torque test.
Routine Test:
  • H.V. Test at 3.75 kV (rams) for one minute.
  • Insulation resistance test.
  • Mechanical insertion & withdrawal test.

 Technical specifications

Type/Data

60/80A SP

100A SP

60/80A SPN

100A SPN

100A TPN

Rated Operating Voltage Ue

415V

415V

415V

415V

415V

Rated Operational Current in

60/80A

100A

60/80A

100A

100A

Rated Insulation Voltage Ui

660V

660V

660V

660V

660V

Rated Short Time Current Lcw

12 kA Peak 0.02 Sec

18 kA Peak 0.02 Sec

12 kA Peak 0.02 Sec

18 kA Peak 0.02 Sec

18 kA Peak 0.02 Sec

Impulse Voltage U imp

6 kV with 1.2/50µs waveform

6 kV with 1.2/50µs waveform

6 kV with 1.2/50µs waveform

6 kV with 1.2/50µs waveform

6 kV with 1.2/50µs 6 kV with 1.2/50µs waveform

Cable Size upto

35 sq. mm

35 sq. mm

35 sq. mm

35 sq. mm

35 sq. mm

Fuse Link Cartridge

As Per BS 1361 Type II a

As Per BS 1361 Type II b

As Per BS 1361 Type II

As Per BS 1361 Type II b

As Per BS 1361 Type II b

Sealing Arrangement Provided

Yes

Yes

Yes

Yes

Yes


Enter Buying Requirement Details
Email Id
Mobile number

Other Products in 'LV Electrical Cutouts' category



Back to top